Hobart 5359D Operation And Maintenance Manual page 133

Engine-driven generator set
Table of Contents

Advertisement

OM 2012
(bb) Coiinect
t!;e genergtor
output
! o c buianced,
three-phase
load of 30
kilowatts.
(CC)
Witfl
gerierator
running
at
115
\I
AC no load,
&perate the contactor
"on-off"
switch
(20,
Fig.
2).
if the average phase voit~gc: charged
more than 1. volt,
or if outpuf
is unsteady,
adjust
"damp" and "rate".
(dd) Turn
the "damp" (1,
Fig.
7) arlj3stir.g
screw CLOCK\;r'ISE
io Improve
response.
Turn
COUNTERCLOCKWiSE
to
improve
STABltiTY.
Gen-
erally
the best adjustment
is approximutely
3/4 of full
CLOCKWISE
travel.
(ee) Turn
the "rate"
(2) adjusting
'screw to near full
COUNTERCLOCKWISE
posit ion.
Turn
the screw siowly
CLOCKWISE
until
the vollcge
output
abruptly
becomes STEADY.
Continue
turning
the screw CLOCKWISE
5 deg to 10 deg past this point
for bcst.'"rote"
adjustment.
L
(ff)
Tighten
adju:ting
screw
locknuts
after adjustment
is
compteted.
C.
Basic Engine
Ad justmcnts
Adjustment
procedures
applicable
to the diesel
engine are included
in the Detroit
Diesel
OpcrGtor's
Manual,
which
is located
in Chapter
6.
Specific
information
for this particular
engine
cpplication
is listed
in Figure
8.
(1)
Exhaust
valve
adjustment
Refer
to the Detroit
Diesel
Operator's
Manual.
(2)
Exhaust
valve
bridge adjustment
Refer
to the Detroit
Diesel
Operator's
Manual.
(3)
Fuel
injector
timing
adjustment
Refer
to the Detroit
Diesel
O'perator's
Manual..
Injector
NOS.
Timing
Gage Tool
No.
J1242.