Hobart 5359D Operation And Maintenance Manual page 131

Engine-driven generator set
Table of Contents

Advertisement

OM 2012
*
8
1.
2.
3.
4.
5.
6.
7.
8.
V.oJtagc adjusting
rheostat
Cable
iength compensation
rheostat
Cable s ize compensation
rheas tct
On-off switch,
Jine-drop
compensation
Fuse (5 Amp)
Fuse h older
Damp (gain) adjusting
potentiometer
Rate adjusting
potentiometer
Voitage
Regulator
Adjustments
Figure
6
,
(dd) Apply a full
load (90 KVA,
260
A) to the generator.
Observe
AC
voltmeter.
If the voltage
observed varies
more than 1% (plus or
minus) from 115 V AC,
adjust rheostats
(2) and (3) slightly
to obtain
a voltage
of 115 V AC,
or as close to this value
as possible.
Turn
knobs CLOCKWISE
to INCREASE
voltage
and COUtdTERCL@CI<WJSE
to DECREASE.
Turn
each knob a small amount at a time to determine
which
rheostat
is having
the most effect
on output
voltage
and re-
quires
adiustment.
Aug 25,%
(c)
Miust
"damp" and "rate"
adjusting
potentiometers
(see Figure
7).
Damping
adiustments
are very delicate
and should not be attempted
unfess
the generator
output
average phase value varies
more than 1 volt,
or
output
voltage
is unstable.
"Damp"
and "rate"
adiustments
must be mcde
in coniunction
with each other because the adiustment
of one may affect
the other.
For example,
improving
the response by .adjusting
the "damp"
potentiometer
(1) may affect
the stability
as adjusted
by the "rate"
potentiometer
(2).
Adjust
as follows:
2-3