Troubleshooting
Alarm
Code
Code 1: 0x0020H
Code 1: 0x0040H
0800H
Code 1: 0x0080H
Code 1: 0x0100H
10000H
-
20000H
-
80000H
Code 2: 0x0200H
ABH2013IQM01_A - Installation and Operation Manual
Description
Hardware fault in the DC/DC. phase
HW fault in the DC/AC. conversion
phase
Hardware fault in the VAC sensor.
Hardware fault in the residual
current sensor.
Inverter overload. The inverter
is supplying more power than
its maximum power in the
consumption grid.
Short circuit in the consumption
grid output.
Error communicating with the
storage system manager.
Solution
Check the installation in the DC and AC part.
Disconnect the DC and AC inverter. Wait until the LEDs
go off and re-connect.
If the error persists, contact the Technical Service.
Check the installation consumptions.
Check the consumption grid installation.
Check the CAN communication wiring of the storage
system management system.
Make sure that the storage system starts via the
display (see section "20.9. Further options").