Chapter 3. Installation and Start-up: Rack-based and RX7i Embedded Interface

Module Installation

3.2
For general information about module and system installation, or if the installation requires CE Mark
compliance, refer to the PACSystems RX7i Hardware Installation Manual, GFK-2223 or the PACSystems RX3i
System Manual, GFK-2314.

Installing an RX7i CPU with Embedded Ethernet Interface

Do not insert or remove the CPU module with power applied. This could cause
the CPU to stop, damage the module, or result in personal injury.
1.
Record the 12-digit hexadecimal MAC Address from the printed label located on the rear wall of CPU
battery compartment. The label is visible when the battery is removed from its compartment. (The battery
does not need to be disconnected to temporarily remove it from the compartment.) For compatible
batteries and battery installation procedures for specific CPUs, refer to the PACSystems RX3i and RX7i
Controllers Battery Manual, GFK-2741.
2.
Install the CPU in the rack. Refer to PACSystems RX7i Hardware Installation Manual, GFK-2223 for
installation instructions.
3.
Set the PLC to Stop mode via the Run/Stop switch or the programming software.

Installing an RX7i Ethernet Interface Module

1.
Record the 12-digit hexadecimal MAC Address from the printed
label on the Ethernet Interface. The label is visible only with
module out of the rack.
2.
Be sure the rack power is OFF.
3.
Slide the module into the slot for which it was configured in the
system. (Must go into main rack.)
4.
Press the module firmly in place, but do not force the module.
Tighten the screws on the top and bottom tabs.
5.
Connect one or both of the network ports on the Ethernet
Interface to the Ethernet network.
6.
Turn on power to the PACSystems rack.
7.
Set the PLC to Stop mode via the Run/Stop switch or the
programming software.
24
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
Warning
MAC Address Label

Figure 7: MAC Address on RX7i

GFK-2224Q