Exchange Status Word Error Codes

The following table shows the error codes that can be written to the Exchange Status word in the Producer (P)
and Consumer. The Exchange Status Word value for each exchange may be displayed via the STAT G Station
Manager command.
Value
(Dec.)
P/C
Error
No new status
0
P/C
event has
occurred.
No error
1
P
currently exists.
No error, data
1
C
consumed.
3
C
SNTP error.
Specification
4
P/C
error.
Stale or invalid
5
C
data sample
Refresh timeout
6
C
without data.
Data after
7
C
refresh timeout.
IP Layer not
10
P/C
currently
initialized.
Lack of resource
12
P/C
error.
Data size
14
C
mismatch error
Loss of Ethernet
18
P/C
Interface error
Major signature
30
C
mismatch
Note:
PACSystems does not support EGD exchange status values 16, 22, 26 and 28. These
exchange status values were used in Series 90 products only.
Exchange configuration occurs when either 1) Hardware Configuration containing EGD is stored to the PLC,
12
2) a PLC containing EGD configuration powers up, or 3) an Ethernet Interface configured for EGD is restarted.
GFK-2224Q
Produced: Initial value until the first producer period refresh occurs.
Consumed: The data has not been refreshed since the previous
consumption scan and the consumer timeout has not expired.
The exchange is producing data.
This value should be ignored in the Output Disabled PLC modes.
The data has been refreshed on schedule since the previous consumption.
The Ethernet Interface in the producer is configured for network time
synchronization, but is not synchronized to an SNTP server. The data was
refreshed on schedule.
During exchange configuration, an invalid configuration parameter was
received by the Ethernet Interface or an error occurred in communication
with the PLC CPU.
The producer has indicated that the data sent was stale or otherwise not
valid at the time it was produced.
The exchange's timeout period is configured to a non-zero value and the
data has not been refreshed within the timeout period.
The data has been refreshed since the previous consumption, but not
within the timeout period.
This status can be set during exchange configuration
Interface detects that it cannot currently access a network. This
temporary status can change if successful network access becomes
possible.
Local resources are not available to establish the exchange during
exchange configuration
the specific error.
The data size of a consumed exchange does not match the exchange
definition. The exchange is ignored.
This error can occur if the CPU no longer recognizes the Ethernet Interface
within the PLC rack. A loss of module PLC Fault Table entry will also be
present. The error can also occur if the module in the given slot of the PLC
rack does not match the module specified in the configuration
(configuration mismatch).
Producer and consumer signatures are different, indicating a mismatched
configuration. The exchange is ignored.
January 2017
Chapter 5. Ethernet Global Data
Description
. The PLC Fault Table may provide more detail on
12
if the Ethernet
12
93