(Word 20) Remote Server - Network Address Length: Word 20 specifies the length in words of the remote PLC
IP address in this COMMREQ Command Block. Word 20 must contain 4.
(Words 21 – 24) Remote Server - IP Address: Words 21–24 specify the four integers, one integer per word, of
the dotted-decimal IP address of the remote PLC to be accessed.

Masked Write to EGD Exchange (4004)

6.9
The Masked Write to EGD Exchange command can be used to write one or more bits in a single byte of a
configured Ethernet Global Data exchange in a remote producer node. EGD protocol prohibits writing to a
consumed exchange. This command can be sent to PACSystems PLCs and to other EGD Class 2 devices.
In a PACSystems PLC, writing an EGD exchange modifies the PLC reference memory locations configured to be
transferred at the specified offset in the exchange. Thus current process data will be updated, not the data that
was transferred last in the exchange.

Masked Write EGD Exchange Command Block

Word Offset
Word 1
Length of command data block
Word 2
0
Word 3
(See table on page 95)
Word 4
0-based
Word 5
0
Word 6
0
Word 7
4004 (fa4H)
Word 8
Retry time, in milliseconds
Word 9
Bit mask, set bit to be written to 1,
rest to 0
Word 10
Write 0 or 1 to selected bit.
Word 11
Remote signature
Word 12
Remote Producer ID (least
significant word)
Word 13
Remote Producer ID (most
significant word)
Word 14
Remote Exchange ID (least
significant word)
Word 15
Remote Exchange ID (most
significant word)
Word 16
Remote Exchange Offset
Word 17
Network address type
Word 18
Network address length
Word 19 to
IP Address of the remote PLC
Word 22
Word 23
Reserved
106
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
Value
13
Description
Always 17
Always 0 (no-wait mode request)
Memory type of COMMREQ Status Word
Offset of COMMREQ Status Word
Reserved
Reserved
Masked Write to EGD Exchange command number.
The time between retries of command transfers. Default is
1000ms.
The bit mask selects the individual bit to be written. The
most significant bytes of Word 9 and Word 10 are ignored.
Value to set the bit selected by the bit mask in Word 9.
EGD Exchange signature. This should be 0 for PLCs when
not using signatures. If run-mode store of EGD will be
used, the use of signatures is highly recommended.
EGD Producer ID
EGD Exchange ID
Byte offset (0-based) in the exchange that should be read.
Must be 1. Indicates an IP address will be used.
Must be 4 for IP address.
Group ID (multicast) is not permitted.
Four integers, specified as one integer per word of the
dotted-decimal IP address of the remote PLC. May not be
a group IP address.
Always 0.
GFK-2224Q