Figure 61: Commreq Ladder Logic Segment (Continued) - GE RX3i User Manual

Pacsystems
Hide thumbs Also See for RX3i:
Table of Contents

Advertisement

Chapter 9. Modbus/TCP Client
10
11
Rung # 10: The COMMREQ Function Block has three input parameters and one output parameter.
The IN field points to the starting location of the Command Block parameters (%R00301 in this example).
The SYSID field of the COMMREQ Function Block defines the target rack and slot of the Ethernet interface to
receive the command data. This is a hexadecimal word value that gives the rack (high byte) and slot (low
byte) location of the Ethernet interface module.
The TASK field of the COMMREQ Function Block indicates which mailbox task ID to use for the specified rack
and slot. For the RX3i and Rx7i ETM001 Ethernet interfaces TASK must always be set to zero. For
PACSystems CPU embedded Ethernet interface, TASK must be set to 65536 (0x10000) to address the CPU's
Ethernet daughterboard.
The FT output (energizes the READ_FLT coil in this example) is turned ON (set to 1) if there were problems
preventing the delivery of the Command Block to the Ethernet interface. In this case, the other status
indicators are not updated for this COMMREQ.
Rung # 11: When ETH_READY is set the CRS word for the Modbus/TCP Read COMMREQ is monitored for a
status of 1, indicating that the Read COMMREQ completed successfully. The CRS word change to 1 sets coil
READ_SUCCESS.
166
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual

Figure 61: COMMREQ Ladder Logic Segment (continued)

GFK-2224Q

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rx7i

Table of Contents