10.1 Application Logic To Control The Opc Ua Server; Opc Ua Server Service Request - GE RX3i User Manual

Pacsystems
Hide thumbs Also See for RX3i:
Table of Contents

Advertisement

Chapter 10. OPC UA Server

10.1 Application Logic to Control the OPC UA Server

The OPC UA server is controlled by means of a service request (SVC REQ function block). The service request
allows you to start, stop, restart and clear OPC specific information.

OPC UA Server Service Request

There is one service request dedicated to the PACSystems OPC UA Server. This is service request 130, protocol
0x0001. The OPC UA Server service request contains a number of sub-functions to accomplish different tasks.
SERVICE_REQUEST 130 protocols:
Sub-function
OPC UA SERVER
Note:
All other protocol codes are reserved, and if used, the SVC_REQ function will not pass
power.
SERVICE_REQUEST 130, protocol 1, sub-functions:
Sub-function
START
STOP
CLEAR
SERVER_STATUS
CONFIG_STATUS
RESTART
Note:
All other sub-functions are reserved; if used, the SVC_REQ function does not pass power.
174
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
Code
16#0001
Code
16#0000
16#0001
16#0002
16#0003
16#0004
16#0005
GFK-2224Q

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rx7i

Table of Contents