Optional Modules

1.5.4 Addressable Device Accessories
E.O.L. Resistor Assemblies
The 47K End-of-Line Resistor Assembly is used to supervise the MMF-300, MDF-300, MMF-301 and CMF-300
module circuits. The 3.9K End-of-Line Resistor Assembly is used to supervise the MMF-302 module circuit. The
resistors are included with each M300 and C304 module.
E.O.L. Power Supervision Relay
The UL listed End-of-Line Power Supervision Relay is used to supervise the power to 4-wire smoke detectors and
notification appliances.
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate which is required for use in Canada.
An ELR, which is supplied with each module and fire alarm control panel, is mounted to
the ELR plate. Resistors mounted to the N-ELR plate can be used for the supervision of
a monitor and control module circuit.
1.6
Optional Modules
The MS-9200 main circuit board includes option module connectors which are located on the right side of the board.
Available option modules include the following:
ACM-8RF Relay Control Module
The ACM-8RF Relay Control Module contains eight high current (5 amps) Form-C relays. The module interfaces to
host fire alarm control panels which employ an ACS (EIA-485) annunciator communications bus. ACM-8RF mod-
ules may be connected to the EIA-485 bus up to 6,000 feet (1,800 m) away from the host control panel. Power-lim-
ited, filtered, nonresettable power must be supplied by the host FACP or a UL listed power supply such as the FCPS-
24F. Refer to Figure 2-14, "ACM-8RF Relay Control Module Installation," on page 32, for wiring details.
RTM-8F Relay Module
The RTM-8F Relay/Transmitter Module plugs into connector J6 and mounts on the bottom right side of the MS-9200
main circuit board. When the module is installed, jumper JP4 must be cut in order to provide module placement
supervision. The RTM-8F provides eight high current (5 amps) Form-C relays. These relays track software zones 1
through 8. The Relay/Transmitter Module also provides Municipal Box or Remote Station transmitters. An
MS-9200 equipped with an RTM-8F meets NFPA 72 codes for Auxiliary and Remote Station requirements. In
remote station applications, the RTM-8F can be configured to transmit alarm only or alarm and trouble signals. Dis-
able switches and indicators are provided on the module. Refer to Figure 2-15, "RTM-8F Module Installation," on
page 33 and Figure 2-16, "RTM-8F Relay Transmitter Module," on page 34, for additional information.
Printer/PC Interface - TB7
The Printer/PC Interface may be used to permanently connect a printer to the MS-9200 for the purpose of printing a
history report, walktest file or program listing or smoke detector data. Printers require separate primary AC power.
The printer connects to TB7 on the main circuit board. TB7 is also used to connect a computer for upload/download
of programming data. Refer to the PK-9200W Off Line Programming Utility Manual for programming information.
Refer to Figure 2-18, "Remote Serial Printer and Computer Connections," on page 36, for information on connec-
tions and "System Edit" on page 45, for information on programming the MS-9200 for use with a printer or PC.
Switch SW3, located on the main circuit board, must be placed in the RS-232 PC/Printer position (down) when con-
necting a printer or PC to TB7.
Older versions of the MS-9200 main circuit board will not have connector TB7. These boards require connection of
a PIM-24 module to the serial EIA-232 port on the printer using cable P/N 75267, in order to connect a printer or PC.
The module mounts to the J11 connector on the MS-9200 main circuit board. Note that the PIM-24 option cannot
be used simultaneously with the DIM-485/LCD-40 option.
16
Document #51003
Rev.E
01/11/02
P/N 51003:E