Specifications
10.3 Fuse Specifications
10.3.1 Branch Circuit Protection Fuses
For compliance with IEC/EN 61800-5-1 electrical standards the following fuses are recommended.
F F requency
converter
200-240 V - T2
1K1-1K5
2K2
3K0
3K7
5K5
7K5
11K
15K
18K5
22K
30K
37K
45K
380-480 V - T4
1K1-1K5
2K2-3K0
4K0-5K5
7K5
11K-15K
18K
22K
30K
37K
45K
55K
75K
90K
1) Max. fuses - see national/international regulations for selecting an applicable fuse size.
Table 10.9 EN50178 fuses 200 V to 480 V
inverter.ru
(812) 702-47-50
VLT Refrigeration Drive FC 103 1.1-90 kW Operating Instructions
Maximum fuse size
1
16A
1
25A
1
25A
1
35A
1
50A
1
63A
1
63A
1
80A
1
125A
1
125A
1
160A
1
200A
1
250A
1
10A
1
16A
1
25A
1
35A
1
63A
1
63A
1
63A
1
80A
1
100A
1
125A
1
160A
1
250A
1
250A
MG16E202 - VLT® is a registered Danfoss trademark
Voltage
Type
200-240
type gG
200-240
type gG
200-240
type gG
200-240
type gG
200-240
type gG
200-240
type gG
200-240
type gG
200-240
type gG
200-240
type gG
200-240
type gG
200-240
type gG
200-240
type aR
200-240
type aR
380-500
type gG
380-500
type gG
380-500
type gG
380-500
type gG
380-500
type gG
380-500
type gG
380-500
type gG
380-500
type gG
380-500
type gG
380-500
type gG
380-500
type gG
380-500
type aR
380-500
type aR
10
10
81
Need help?
Do you have a question about the VLT FC 103 and is the answer not in the manual?
Questions and answers