Danfoss VLT FC 103 Operating Instructions Manual page 84

Vlt refrigeration drive fc 103 1.1-90 kw
Hide thumbs Also See for VLT FC 103:
Table of Contents

Advertisement

Specifications
Environment
Enclosure
Vibration test
Max. relative humidity
Aggressive environment (IEC 60068-2-43) H
Ambient temperature
1)
Only for
2)
As enclosure kit for
3)
Derating for high ambient temperature, see special conditions in the Design Guide
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Derating for high altitude, see special conditions in the Design Guide
EMC standards, Emission
EMC standards, Immunity
See section on special conditions in the Design Guide.
Control card performance
Scan interval
Control card, USB serial communication
USB standard
USB plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is not galvanically isolated from protection earth. Use only an isolated laptop as PC connection to
10
10
the USB connector on the frequency converter.
Protection and Features
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches a
predefined level. An overload temperature cannot be reset until the temperature of the heatsink is below the
values stated in the tables on the following pages (Guideline - these temperatures may vary for different power
sizes, frame sizes, enclosure ratings etc.).
The frequency converter is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit
voltage is too low or too high.
The frequency converter constantly checks for critical levels of internal temperature, load current, high voltage on
the intermediate circuit and low motor speeds. As a response to a critical level, the frequency converter can adjust
the switching frequency and/ or change the switching pattern in order to ensure the performance of the
frequency converter.
80
inverter.ru
(812) 702-47-50
3)
3.7 kW (200-240 V),
7.5 kW (380-480 V)
3.7 kW (200-240 V),
MG16E202 - VLT® is a registered Danfoss trademark
VLT Refrigeration Drive FC 103 1.1-90 kW Operating Instructions
5-93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
7.5 kW (380-480 V)
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
1)
2)
IP20
/Type 1, IP21
/Type 1, IP55/Type 12, IP66
Max. 50 C (24-hour average maximum 45 C)
EN 61800-3, EN 61000-6-3/4, EN 55011
EN 61800-3, EN 61000-6-1/2,
USB type B "device" plug
1.0 g
class Kd
0 C
- 10 C
-25 - +65/70 C
1000 m
1 ms
1.1 (Full speed)