Fcm Motor Specifications; Fuse And Circuit Breaker Specifications - Danfoss VLT DriveMotor FCM 106 Design Manual

Hide thumbs Also See for VLT DriveMotor FCM 106:
Table of Contents

Advertisement

Specifications

6.8 FCM Motor Specifications

Motor output (U, V, W)
Output voltage
Output frequency, asynchronous motor
Output frequency, PM motor
Switching on output
Ramp times
Thermistor input (at motor connector)
Input conditions

6.9 Fuse and Circuit Breaker Specifications

Overcurrent protection
6
6
Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be
carried out according to local and national regulations. Fuses must be designed for protection in a circuit capable of
supplying a maximum of 100,000 A
circuit capable of supplying a maximum of 10,000 A
circuit breaker.
UL/Non UL Compliance
Use the circuit breakers or fuses listed in Table 6.13, to ensure compliance with UL or IEC 61800-5-1.
Circuit breakers must be designed for protection in a circuit capable of supplying a maximum of 10,000 A
480 V maximum.
In the event of malfunction, failure to follow the protection recommendation can result in damage to the frequency
converter.
58
®
VLT
DriveMotor FCP 106 and FCM 106 Design Guide
(symmetrical), 480 V maximum. Circuit breakers must be designed for protection in a
rms
(symmetrical), 480 V maximum; or the value rated on the individual
rms
MG03M102 - 08/2015
0-100% of supply voltage
plus
0-200 Hz (VVC
), 0-400 Hz (u/f)
0-390 Hz (VVC
plus
PM)
Unlimited
0.05-3600 s
Fault: >2.9 kΩ, no fault: <800 Ω
(symmetrical),
rms