Description
See equipment label for the maximum ambient operating temperature limits
Humidity levels must be 5-95% non-condensing
Check for proper fusing or circuit breakers
Check that all fuses are inserted firmly and in operational condition and that all circuit breakers are
in the open position
The unit requires an earth wire (ground wire) from its chassis to the building earth (ground)
Check for good earth connections (ground connections) that are tight and free of oxidation
Earthing (grounding) to conduit or mounting the back panel to a metal surface is not a suitable
earth (ground)
Check for loose connections
Check that motor and mains are in separate conduit or separated screened cables
Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion
Ensure that all switch and disconnect settings are in the proper positions
Check that the unit is mounted solidly or that shock mounts are used, as necessary
Check for an unusual amount of vibration