Hand Control macro

This macro configures for drive control using only the control panel with no
automated control. Typically, this is a temporary configuration used prior to control
wiring.
9902
1001
1002
1106
1201
1504
1510
1608
Application macros
X1
Signal cable shield (screen)
1
SCR
Not configured
2
AI1
Analog input circuit common
3
AGND
Reference voltage 10 VDC
4
10V
Not configured
5
AI2
Analog input circuit common
6
AGND
Output frequency: 0(4)...20 mA
7
AO1
mA
Output current: 0(4)...20 mA
8
AO2
mA
9
AGND
Analog output circuit common
Auxiliary voltage output +24 VDC
10 24V
Auxiliary voltage output common
11 GND
Digital input common for all
12 DCOM
Not configured
13 DI1
Not configured
14 DI2
Not configured
15 DI3
Not configured
16 DI4
Not configured
17 DI5
Not configured
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
Parameters Changed Relative to HVAC Default
Parameter
14 (
APPLIC MACRO
1
0 (
EXT
COMMANDS
2
0 (
EXT
COMMANDS
2
2 (
REF
SEL
0 (
CONST SPEED SEL
1
0.0 mA
MINIMUM AO
2
0.0 mA
MINIMUM AO
1
0 (
START ENABLE
Relay output 1 (P 1401)
Default operation: Started =>19 connected to 21
Relay output 2 (P 1402)
Default operation: Running =>22 connected to 24
Relay output 3 (P 1403)
Default operation: Fault (-1) =>25 connected to 27
(Fault => 25 connected to 26)
Value
)
3415
HAND CONTROL
)
3416
NOT SEL
)
3417
NOT SEL
2)
3419
AI
)
3420
NOT SEL
3421
4010
)
4110
NOT SEL
A
550-UH User's Manual
J1
Jumper Settings
...
AI1: 0(4)
20 mA
...
AI2: 0(4)
20 mA
Parameter
3
0 (
SIGNAL
PARAM
NOT SEL
3
0
SIGNAL
MIN
3
0
SIGNAL
MAX
3
OUTPUT
UNIT
NO UNIT
3
0.0
OUTPUT
MIN
3
0.0
OUTPUT
MAX
1 (
SET POINT SEL
AI
1 (
SET POINT SEL
AI
ON
1
2
Value
)
1)
1)