EVER UPS POWERLINE RT 6000 / 10000 series instruction manual
Overload in the output
Overload in the output circuit.
Alarm code: 41
The UPS unit has entered the bypass mode or
Inverter overload
the failure mode due to overload in the inverter
Alarm code: 42
(frequency converter) mode.
Overload in the
The UPS cuts off the power and enters the failure
bypass mode
mode due to overload in the bypass or ECO
mode.
Alarm code: 43
Short circuit in the
The UPS unit has detected an improperly low
output
output impedance level, which has been
recognized as a short circuit.
Alarm code: 31
Fan failure
The fan does not operate normally.
Alarm code: 84
Radiator temperature
Radiator temperature is too high. The UPS unit
too high
operating in excessive temperatures can cause
damage to the unit.
Alarm code: 81
Ambient temperature
Environment temperature is higher than the
too high
specified UPS operation temperature.
Alarm code: 82
Too high voltage on
An overvoltage has occurred on the bus of the
the bus
UPS unit.
Alarm code: 21
Voltage drop on the
A voltage drop has occurred on the bus of the
bus
UPS unit.
Alarm code: 22
Bus voltage
Positive and negative voltages on the bus are too
unbalanced
asymmetric and can cause a minor fault
Alarm code: 23
Short circuit on the
bus
Violent decrease of bus voltage
Alarm code: 24
Failure of the soft
start of the bus
Soft start of the bus has failed.
Alarm code: 25
61
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
Disconnect some receivers from the UPS unit. The
UPS unit will still operate but if the load is increased
(above the specified level) it may switch to bypass
mode. The alarm is deactivated once that issue is
solved.
To reduce the load at the output of the UPS unit,
disconnect some receivers.
Disconnect some receivers from the UPS unit.
Disconnect all receivers from the UPS unit. Switch off
the UPS unit. Check if a short circuit occurred in the
UPS unit or in the receivers. Make sure that the short
circuit is removed before switching the device back
on.
Check the UPS unit fans.
If the UPS unit entered the bypass mode and the
temperature is still too high, the unit should be
switched off. Uncover the vents and remove all heat
sources. Wait until the UPS unit cools down. Ensure
free air circulation around the UPS unit. Restart the
UPS unit.
Provide the recommended environment temperature
using e.g. air conditioning in the room.
If the UPS unit is powering a device, it will switch to
the bypass mode. Contact service support.
If the UPS unit is powering a device, it will switch to
the bypass mode. Contact service support.
If the UPS unit is powering a device, it will switch to
the bypass mode. Contact service support.
Contact service support.
Contact service support.