5 Functional Mechanisms of this Application
5.2 Change-over to the "Siemens Telegram 1" frame
(with FB11)
5.2
Change-over to the "Siemens Telegram 1" frame
(with FB11)
FB11 "PZD_G120_Tel_1" is, like FB10 "PZD_G120_Tel_352", intended for
transmission of process data, however, it expects message frame "Siemens
Telegram 1" instead of "Siemens Telegram 352".
The "Telegram 1" frame only transfers two words in any direction: control word and
setpoint value or status word and actual value.
Figure 5-7 FB 11 " PZD_G120_Tel_1"
To switch over to message frame 1, you have to:
select message frame 1 for SINAMICS G in HW Config,
call FB11" PZD_G120_Tel_1" in OB1 instead of FB10 "PZD_G120_Tel_352",
load the program folder into the SIMATIC S7-300/400F CPU again (inc. system
data, see Table 3-3 step 9),
change the interface configuration of SINAMICS G to message frame 1 in the
STARTER (see Tabelle 6-2, step 13)
adjust the HMI.