4 Operation of the Application

4.1 Requirements

4
Operation of the Application
4.1
Requirements
To be able to switch on the SINAMICS G via the digital inputs, the following points
must be fulfilled:
If the yellow "SAFE" LED is flashing on the SINAMICS G, a safety function is
active and the SINAMICS G cannot be switched on (see chap. 4.2.2).
When using an IOP, please check that the network icon (
the top right. If the hand icon (
button (
When using a BOP-2, please check whether the hand icon (
yes, press the Hand/Auto button (
4.2
Operation of the Application
The SINAMICS G is exclusively moved via digital inputs. The HMI is only used for
monitoring.
4.2.1

Operating the standard functions

Table 4-1
Signal
E 0.0
E 0.1
E 0.2
E 0.3
E 0.4
E 0.5
E 0.6
E 0.7
SINAMICS G120C at S7-300/400F-DP
Beitrags-ID: 60441457,
V2.2,
).
Name
On
Switching the SINAMICS G on/off,
(Off2 and Off3 =1 must apply for the operation)
Off 2
0= Motor immediately switched off, the motor spins out
Off 3
0= Fast stop, motor is decelerated with Off3 ramp down time (P1135) until it
stops
Ack
Rising edge acknowledges a pending error in the SINAMICS G and
reintegrates passivated safety modules
S-Test
Starts the self-test of the extended safety functions of the SINAMICS G
0
The setpoint value is set to 0.
n+
The setpoint value is increased
n-
The setpoint value is decreased
11/2014
) is displayed there, press the Hand/Auto
).
Function
) is displayed on
) is displayed. If