6 Configuration and Settings
6.2 Configuring the SINAMICS G drive
No.
Action
18.
Enable the transfer of the
inputs
This activates the "Telegram
900" frame in the SINAMICS
G120, without enable the
"PROFIsafe Telegram 30"
frame is used.
Select the inputs to be
transferred by closing the
connection
19.
Set the enable of the safety
functions
Open the "Configuration"
dialog
20.
In the "PROFIsafe address"
field you enter the value you
noted down during the
S7-300F configuration (step
12
in Tabelle
Select bit 15 of the control
word (i.e. "P2090.15") as
the "Test stop selection"
Set the monitoring of the
forced dormant error
detection for the expanded
functions to 8h.
Press "Close" to close the
dialog box.
21.
Open the "Safe torque off
(STO)" dialog, by clicking on
the button "Safe basic
functions (STO, SBC)", and
deactivate the monitoring of
the "Forced dormant error
detection" for the basic
functions by setting the
monitoring time to the
maximal value (9000 h).
Press "Close" to close the
dialog box.
SINAMICS G120C at S7-300/400F-DP
Beitrags-ID: 60441457,
V2.2,
6-1)
Monitoring the "Forced dormant error detection" of the basic
functions is not necessary when using the extended
functions, since the test of the extended functions contains
the test for the basic functions.
11/2014