4 Operation of the Application
4.3 Monitoring and parameter access via operator panel
Table 4-4
7.
Select the access type with the "Read
parameters" and "Write parameters"
buttons.
8.
Read parameters:
Proceed with point 3 in the table.
Write parameters:
When tapping or clicking the yellow
input field for the ramp-up/ramp-down
time, a keyboard mask for the value
input opens. Close your input with the
Return key.
9.
Start the write or read job with the
"Start" button.
10.
Click "Start" again to terminate the
transmission requirement.
Note
If you wish to check the parameters after a write job, you must trigger an
additional read job.
SINAMICS G120C at S7-300/400F-DP
Beitrags-ID: 60441457,
V2.2,
Action
11/2014
Comment
The selected access type is displayed
via a bright green button.
The job status specifies how the job
was completed:
done = completed without errors
errori
= job cancelled with error
The status refers to processing the
system function blocks SFB 52
"RDREC" and SFB 53 "WRREC" in
STEP7 code. For fault diagnostics see
/3/.
done and
drive_errori
means that the
job was transferred without error,
however, SINAMICS G could not or only
partially process the job.
The error codes are available in
6.1.5.1
"Configuring the fieldbus,
Communication via PROFIBUS, Acyclic
communication" in the operating
instruction (/7/).
The bits of the job status are deleted as
soon as the transmission requirement is
no longer pending.
8,0
chapter
39