Operation At Rated Voltage; Operating Under Light-Load Conditions - Siemens SINAMICS SL150 Reference Manual

Medium-voltage drive
Hide thumbs Also See for SINAMICS SL150:
Table of Contents

Advertisement

3.2.10

Operation at rated voltage

Fundamentals
The function of the power semiconductor module is tested under the following conditions:
● Operation with resistive load
● Rated voltage
● Reduced current >5 A
Test procedure
1. The auxiliary voltage is present.
2. The power semiconductor module is operated in controlled mode as a B6 bridge with torque
3. The output current and output voltage are measured at the output of the power
Result
The test is passed if the defined values are measured at the output of the power semiconductor
module.
3.2.11

Operating under light-load conditions

Fundamentals
The function of the power semiconductor module is tested under the following conditions:
● Operation with resistive load
● Voltage of 50 Hz 400 V +150 V / -50 V 3AC
● Load current of 300 A ±100 A
Test procedure
1. The auxiliary voltage is present.
2. The power semiconductor module is operated in controlled mode as a B6 bridge with torque
3. The output current and output voltage are measured at the output of the power
Result
The test is passed if the defined values are measured at the output of the power semiconductor
module.
SINAMICS SL150 6SL3860 F03 F70 F98 F79 F76
Reference Manual Rev.201902141425 SL150 luftgekühlt
directions 1 and 2.
semiconductor module.
directions 1 and 2.
semiconductor module.
Tests
3.2 Function test
27

Advertisement

Table of Contents
loading

This manual is also suitable for:

6sl3860

Table of Contents