Configuring/address space
4.4 Parameters
4.4.5
Parameters for operating in Fast Mode
Parameters of the TM Count 1x24V
The following parameter settings are possible:
Table 4- 8
Settable parameters and their default setting in "Fast Mode" operating mode
Parameters
Reaction to CPU STOP
1
Enable diagnostic inter-
rupt on wire break
2
Enable additional diag-
nostic interrupts
Signal type
Signal evaluation for
counter inputs
Filter frequency for
counter inputs
1
48
Value range
Output substitute value
•
Keep last value
•
Continue operation
•
Deactivated
•
Activated
•
Deactivated
•
Activated
•
Pulse (A)
•
Pulse (A) and direction (B)
•
Count up (A), count down (B)
•
Incremental encoder (A, B
•
phase-shifted)
Incremental encoder (A, B, N)
•
Single
•
Double
•
Quadruple
•
100 Hz
•
200 Hz
•
500 Hz
•
1 kHz
•
2 kHz
•
5 kHz
•
10 kHz
•
20 kHz
•
50 kHz
•
100 kHz
•
200 kHz
•
Default setting
Re-
configura-
tion in
RUN
Output substi-
Yes
tute value
Deactivated
Yes
Deactivated
Yes
Pulse (A) and
Yes
direction (B)
Single
Yes
200 kHz
Yes
Technology Module TM Count 1x24V (6ES7138-6AA00-0BA0)
Effective range with
configuring software
HSP for
HSP for
STEP 7
STEP 7;
(TIA Portal)
GSD file
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Manual, 02/2017, A5E33002339-AB