Interrupts/diagnostic messages
5.2 Diagnostic messages
5.2
Diagnostic messages
Enabling the diagnostic interrupts
You enable the diagnostic interrupts in the basic parameters of the device configuration.
The technology module can trigger the following diagnostic interrupts:
Table 5- 5
Possible diagnostic interrupts
Diagnostic interrupt
Parameter assignment error
•
Hardware interrupt lost
•
Module temporarily unavailable
•
Internal error
•
Watchdog tripped. Module is defective.
•
Wire break at digital input A, B or N
•
Error
•
Load voltage missing
•
Short circuit or overload at external encoder supply
•
Error at the digital outputs
•
Supply voltage error
•
1
Illegal A/B signal ratio
•
Overheating
•
No longer available as of module version V1.2. This case is then taken into account by diagnostic interrupt "Load volt-
1
age missing".
60
Monitoring
Monitoring is always active. A diagnostic interrupt is
triggered each time an error is detected.
Monitoring is active if a push-pull switching encoder
has been configured. A detected error only triggers a
diagnostic interrupt if "Enable diagnostic interrupt for
wire break" has been enabled in the device configura-
tion.
Monitoring is always active. A detected error only
triggers a diagnostic interrupt if "Enable additional
diagnostic interrupts" has been enabled in the device
configuration.
Technology Module TM Count 1x24V (6ES7138-6AA00-0BA0)
Manual, 02/2017, A5E33002339-AB