Interrupts/diagnostic messages
5.2 Diagnostic messages
Diagnostic alarm
Error
code
Hardware interrupt
16
H
lost
Chan-
1F
H
nel/component
temporarily una-
vailable
Internal error
100
Watchdog tripped.
103
Module is defec-
tive.
Short circuit or
10E
overload at exter-
nal encoder supply
Error at the digital
10F
outputs
Supply voltage
110
error
1
Illegal A/B signal
500
ratio
62
Meaning
Module cannot send an interrupt because a
•
previous interrupt has not been processed
Possible cause: Too many hardware inter-
•
rupts in too short a time
Firmware update in progress
•
or update has been canceled.
The module reads no
process values in this state.
Technology module defective
H
Firmware error
H
Technology module defective
Error at encoder supply
•
H
Possible causes:
•
–
Short circuit
–
Overload
Error at the digital outputs
•
H
Possible causes:
•
–
Short circuit
–
Overload
Error at supply voltage L+
•
H
Possible causes:
•
–
Low voltage
–
Wiring of L+ supply voltage defective
Time profile of signals A and B of the in-
•
H
cremental encoder does not meet certain
specifications
Possible causes:
•
–
Signal frequency too high
–
Encoder faulty
–
Process wiring faulty
Remedy
Change interrupt processing in the
•
CPU and re-assign technology module
parameters correspondingly
Check frequency of interrupts from the
•
process
Wait for firmware update
•
If firmware update aborts:
•
–
Check minimum firmware version
required
–
Check supply voltage
–
Repeat firmware update
Replace technology module
Run firmware update
Replace technology module
Check encoder wiring
•
Check consumers connected to en-
•
coder supply
Check wiring at the digital outputs
•
Check consumers connected to the
•
digital outputs
Check supply voltage L+ on the Ba-
•
seUnit
Check wiring of supply voltage L+
•
Check total consumption of the load
•
group
Check process wiring
•
Check encoder/sensor
•
Check parameter assignment
•
Technology Module TM Count 1x24V (6ES7138-6AA00-0BA0)
Manual, 02/2017, A5E33002339-AB