4.1.2

Parameters DI mode

Parameters of the DI 16x24VDC HF in the DI mode
In the table below you will find the parameters in the DI mode. These parameters apply to
channels 0 to 15.
Table 4- 1
Settable parameters and their defaults in the DI mode
Parameter
Diagnostics
No
supply voltage L+
Wire break
Input delay
Hardware interrupt***
Rising edge
Falling edge
Rising and falling edge Yes/No
* If you enable diagnostics for multiple channels, you will receive an alarm surge on failure of the supply voltage because
each enabled channel will detect this fault.
You can prevent this alarm surge by enabling diagnostics for one channel only.
** The scope can be assigned for each channel during parameter assignment in RUN.
*** For the configuration as a 4 x 8-channel module, a maximum of 16 hardware interrupts can be configured (channels 0 to
15).
DI 16x24VDC HF Digital Input Module (6ES7521-1BH00-0AB0)
Manual, 08/2018, A5E03485952-AG
Range of values
Default setting
Yes/No
No
Yes/No
No
0.05 ms, 0.1 ms,
3.2 ms;
0.4 ms, 1.6 ms,
for isochronous
3.2 ms, 12.8 ms,
mode 0.05 ms
20 ms
(cannot be
changed)
Yes/No
No
Yes/No
No
No
Parameters/address space
Parameter
Range of effectiveness with con-
reassignment
figuration software, e.g. STEP 7
in RUN
Integrated in the
hardware catalog
as of STEP 7,
V13 SP1 or GSD
file
PROFINET IO
Yes
Channel*
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
4.1 Parameter
GSD file
PROFIBUS DP
Channel
group**
Channel
group**
Channel
group**
Channel
Channel
Channel
17