4.4

Parameters

4.4.1

Parameter setting

You can use various parameters to define the properties of the technology module.
Depending on the settings, not all parameters are available. When parameters are assigned
in the user program, the parameters are transferred to the module with the "WRREC"
instruction and data record 128 (Page 73).
You have the following options for setting the module's parameters:
Parameter setting via ...
Hardware configuration in STEP 7
(TIA Portal) in centralized operation
with an ET 200SP CPU
Hardware configuration and technol-
ogy object High_Speed_Counter in
STEP 7 (TIA Portal) in "Operating
with technology object "Counting and
measurement"" operating mode
Hardware configuration and technol-
ogy object in STEP 7 (TIA Portal) in
"Position input for technology object
"Motion Control"" operating mode
Technology Module TM Count 1x24V (6ES7138-6AA00-0BA0)
Manual, 02/2017, A5E33002339-AB
Basic procedure
1. Select an appropriate CPU under "Add new device > Controller > SIMATIC
ET 200 CPU".
2. Select the module in the hardware catalog under "Technology modules".
3. Set the device configuration and the parameters of the module in the hardware
configuration.
4. Set the parameters of the technology object.
5. Download the parameter assignment to the module.
1. Select an appropriate CPU under "Add new device > Controller > SIMATIC
S7-1500 / SIMATIC ET 200 CPU"".
2. For distributed operation, select an interface module in the hardware catalog
under "Distributed I/O > ET 200SP > Interface modules".
3. Select the module in the hardware catalog under "Technology modules".
4. Set the device configuration and the parameters of the module (Page 36) in the
hardware configuration.
"Operating with technology object "Counting and measurement"" must be set
as the operating mode.
5. Set the parameters (Page 36) of the High_Speed_Counter technology object.
6. Download the parameter assignment to the module.
1. Select an appropriate CPU under "Add new device > Controller > SIMATIC
S7-1500 / SIMATIC ET 200 CPU"".
2. For distributed operation, select an interface module in the hardware catalog
under "Distributed I/O > ET 200SP > Interface modules".
3. Select the module in the hardware catalog under "Technology modules".
4. Set the device configuration and the parameters of the module (Page 41) in the
hardware configuration.
"Position input for technology object "Motion Control"" must be set as the oper-
ating mode.
5. Set the parameters of the axis technology object.
6. Download the parameter assignment to the module.