The Tools You Need For Installation; Your Operating Environment; The System's Tolerance Of Different Environmental Conditions - Sun Microsystems Netra t1 100 User And Administration Manual

Table of Contents

Advertisement

The Tools You Need for Installation

An 8mm wrench (for assembling the rack mounting)
A small flat-head screwdriver (for installing hard disks)
An ESD pad and an anti-static wrist strap and earthing point (to protect the
components of the system if you need to install any hardware options)
A No 2 Phillips screwdriver (and a No. 1 Phillips screwdriver if you are installing
additional memory)
A Thomas & Betts two-hole lug (part number: 54204-UB) and a Thomas & Betts
crimping tool (part number: TBM 5-S) (you will need these tools if you need to
use a two-hole ground connection; see Chapter 3)

Your Operating Environment

The System's Tolerance of Different
Environmental Conditions
You can operate and store the system safely in the following conditions:
Ambient temperature
Temperature variation
Relative humidity
Altitude
Earthquake
The system conforms to the NEBS requirements for earthquake zone 4
4
Netra t1 User and Administration Guide • June 2000
Operating: 0˚C to 40˚C (temporary operation outside these limits is permitted
for a maximum of 96 hours within the range –5˚C to 55˚C)
Storage: –40˚C to 70˚C
Operating: 30˚C/hr maximum
Storage: 30˚C/hr maximum
Operating: 5% to 85% (non-condensing)
Storage: 10% to 95% (non-condensing)
Operating: –300 m to +3000 m
Storage: –300 m to +12000 m