LXL-1010 Installation and Setup Guide
The keypads will display all zone numbers of wireless units programmed into the system. Fault
each transmitter in turn, causing each one to send a signal. As the system receives a signal from
each of the transmitters, the zone number of that transmitter disappears from the display.
2. After all transmitters have been checked, exit the sniffer mode by keying [Installer code
(4112)] + OFF.
IMPORTANT: Sniffer mode does not automatically expire. You must manually exit Sniffer
mode (by entering [Installer code] + OFF) to return to normal operation.
Notes:
All BR type units must physically be activated to clear the display.
When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other
buttons on that transmitter are cleared. This also applies to 5816 and 5817 transmitters, which
have multiple loops (zones).
Any transmitter that is not "enrolled" will not turn off its zone number.

Go/No Go Test Mode

The Go/No Go Test verifies adequate RF signal strength from the proposed transmitter location, and
allow you to reorient or relocate transmitters if necessary, before mounting the transmitters
permanently. This mode is similar to the Transmitter Test mode, except that the wireless receiver
gain is reduced. This will enable you to make sure that the RF signal from each transmitter is
received with sufficient signal amplitude when the system is in the normal operating mode.
1. Enter [Installer code (4112)] + [#] + 4.
2. After you have placed transmitters in their desired locations and the approximate length of wire
to be run to sensors is connected to the transmitter's screw terminals (if used), fault each
transmitter. Do not conduct this test with your hand wrapped around the transmitter, as this will
cause inaccurate results.
a. The keypad will beep three times to indicate signal reception and display the appropriate zone
number.
b. If the keypad does not beep, you should reorient or move the transmitter to another location.
Usually a few inches in either direction is all that is required.
4. If each transmitter produces the proper keypad response when it is faulted, you can then
permanently mount each of the transmitters according to the instructions provided with them.
5.

Dialer Communication Test and Periodic Test Reports

1. Enter Installer Code + 5 [ TEST ], then press "1" at the prompt to start the Dialer Test.
1=DIAL, 0=WALK
The following will be displayed (accompanied by 2 beeps) if test is successful:
PHONE OKAY
A Contact ID report will also be sent (code 601)
If the dialer test is unsuccessful, the following is displayed:
COMM FAILURE
2. Enter installer code + OFF to clear the display and exit.

Automatic Periodic Test Report

The system can be set to automatically send test reports (enabled in field *64; Contact ID code 602) at
specified intervals.
13-2
www.PDF-Zoo.com
Exit the Go/No Go Test mode by entering: [Installer code (4112)] + OFF.
(no special display on Fixed-Word keypads; displays "DISARMED READY TO ARM")
("Cd" displayed on Fixed-Word Display Keypads)
("FC" displayed on Fixed-Word Display Keypads)