5.6 GROUPED ELEMENTS
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase injection:
⋅
I
0.2917 I
=
op
injected
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS
VOLTAGE ELEMENTS
5
These protection elements can be used for a variety of applications such as:
•
Undervoltage Protection: For voltage sensitive loads, such as induction motors, a drop in voltage increases the
drawn current which may cause dangerous overheating in the motor. The undervoltage protection feature can be used
5-152
; three-phase injection, opposite rotation:
Figure 5–63: NEGATIVE SEQUENCE IOC1 SCHEME LOGIC
SETTING GROUP 1(6)
PHASE
UNDERVOLTAGE1
PHASE
MESSAGE
UNDERVOLTAGE2
NEUTRAL OV1
MESSAGE
NEUTRAL OV2
MESSAGE
NEUTRAL OV3
MESSAGE
AUXILIARY UV1
MESSAGE
AUXILIARY UV2
MESSAGE
AUXILIARY UV3
MESSAGE
AUXILIARY OV1
MESSAGE
AUXILIARY OV2
MESSAGE
AUXILIARY OV3
MESSAGE
F35 Multiple Feeder Protection System
I
I
).
=
op
injected
VOLTAGE ELEMENTS
See page 5–154.
See page 5–154.
See page 5–155.
See page 5–155.
See page 5–155.
See page 5–156.
See page 5–156.
See page 5–156.
See page 5–157.
See page 5–157.
See page 5–157.
5 SETTINGS
5.6.8 VOLTAGE ELEMENTS
GE Multilin