GE UR F35 Series Instruction Manual page 474

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 28 of 61)
ADDR
REGISTER NAME
Neutral Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5B00
Neutral Time Overcurrent 1 Function
5B01
Neutral Time Overcurrent 1 Signal Source
5B02
Neutral Time Overcurrent 1 Input
5B03
Neutral Time Overcurrent 1 Pickup
5B04
Neutral Time Overcurrent 1 Curve
5B05
Neutral Time Overcurrent 1 Multiplier
5B06
Neutral Time Overcurrent 1 Reset
5B07
Neutral Time Overcurrent 1 Block
5B09
Neutral Time Overcurrent 1 Target
B
5B0A
Neutral Time Overcurrent 1 Events
5B0B
Reserved (6 items)
5B11
...Repeated for Neutral Time Overcurrent 2
5B22
...Repeated for Neutral Time Overcurrent 3
5B33
...Repeated for Neutral Time Overcurrent 4
5B44
...Repeated for Neutral Time Overcurrent 5
5B55
...Repeated for Neutral Time Overcurrent 6
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5C00
Neutral Instantaneous Overcurrent 1 Function
5C01
Neutral Instantaneous Overcurrent 1 Signal Source
5C02
Neutral Instantaneous Overcurrent 1 Pickup
5C03
Neutral Instantaneous Overcurrent 1 Delay
5C04
Neutral Instantaneous Overcurrent 1 Reset Delay
5C05
Neutral Instantaneous Overcurrent 1 Block
5C07
Neutral Instantaneous Overcurrent 1 Target
5C08
Neutral Instantaneous Overcurrent 1 Events
5C09
Reserved (8 items)
5C11
...Repeated for Neutral Instantaneous Overcurrent 2
5C22
...Repeated for Neutral Instantaneous Overcurrent 3
5C33
...Repeated for Neutral Instantaneous Overcurrent 4
5C44
...Repeated for Neutral Instantaneous Overcurrent 5
5C55
...Repeated for Neutral Instantaneous Overcurrent 6
5C66
...Repeated for Neutral Instantaneous Overcurrent 7
5C77
...Repeated for Neutral Instantaneous Overcurrent 8
5C88
...Repeated for Neutral Instantaneous Overcurrent 9
5C99
...Repeated for Neutral Instantaneous Overcurrent 10
5CAA
...Repeated for Neutral Instantaneous Overcurrent 11
5CBB
...Repeated for Neutral Instantaneous Overcurrent 12
Ground Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5D00
Ground Time Overcurrent 1 Function
5D01
Ground Time Overcurrent 1 Signal Source
5D02
Ground Time Overcurrent 1 Input
5D03
Ground Time Overcurrent 1 Pickup
5D04
Ground Time Overcurrent 1 Curve
5D05
Ground Time Overcurrent 1 Multiplier
5D06
Ground Time Overcurrent 1 Reset
5D07
Ground Time Overcurrent 1 Block
5D09
Ground Time Overcurrent 1 Target
5D0A
Ground Time Overcurrent 1 Events
5D0B
Reserved (6 items)
5D11
...Repeated for Ground Time Overcurrent 2
5D22
...Repeated for Ground Time Overcurrent 3
5D33
...Repeated for Ground Time Overcurrent 4
5D44
...Repeated for Ground Time Overcurrent 5
B-36
RANGE
0 to 1
0 to 5
0 to 1
0 to 30
0 to 16
0 to 600
0 to 1
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 30
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1
0 to 30
0 to 16
0 to 600
0 to 1
0 to 4294967295
0 to 2
0 to 1
0 to 1
F35 Multiple Feeder Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
---
1
F122
pu
0.001
F001
---
1
F103
0 (IEEE Mod Inv)
---
0.01
F001
---
1
F104
0 (Instantaneous)
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F122
pu
0.001
F001
---
1
F103
0 (IEEE Mod Inv)
---
0.01
F001
---
1
F104
0 (Instantaneous)
---
1
F300
---
1
F109
---
1
F102
---
1
F001
DEFAULT
0 (Disabled)
0 (SRC 1)
0 (Phasor)
1000
100
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Phasor)
1000
100
0
0 (Self-reset)
0 (Disabled)
0
GE Multilin

Advertisement

Table of Contents
loading