Autoreclose - GE UR F35 Series Instruction Manual

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

5 SETTINGS

PATH: SETTINGS
CONTROL ELEMENTS
 AUTORECLOSE 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin


AUTORECLOSE

AUTORECLOSE 1(6)
AR1 FUNCTION:
Disabled
AR1 INITIATE:
Off
AR1 BLOCK:
Off
AR1 MAX NUMBER OF
SHOTS: 1
AR1 REDUCE MAX TO 1:
Off
AR1 REDUCE MAX TO 2:
Off
AR1 REDUCE MAX TO 3:
Off
AR1 MANUAL CLOSE:
Off
AR1 MNL RST FRM LO:
Off
AR1 RESET LOCKOUT IF
BREAKER CLOSED: Off
AR1 RESET LOCKOUT ON
MANUAL CLOSE: Off
AR1 BKR CLOSED:
Off
AR1 BKR OPEN:
Off
AR1 BLK TIME UPON
MNL CLS: 10.000 s
AR1 DEAD TIME 1:
1.000 s
AR1 DEAD TIME 2:
2.000 s
AR1 DEAD TIME 3:
3.000 s
AR1 DEAD TIME 4:
4.000 s
AR1 ADD DELAY 1:
Off
AR1 DELAY 1:
0.000 s
AR1 ADD DELAY 2:
Off
F35 Multiple Feeder Protection System
5.7 CONTROL ELEMENTS
5.7.6 AUTORECLOSE
Range: Disabled, Enabled
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1, 2, 3, 4
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Off, On
Range: Off, On
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic operand
5
5-169

Advertisement

Table of Contents
loading

Table of Contents