GE UR F35 Series Instruction Manual page 475

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 29 of 61)
ADDR
REGISTER NAME
5D55
...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5DA0
Ground Instantaneous Overcurrent 1 Function
5DA1
Ground Instantaneous Overcurrent 1 Signal Source
5DA2
Ground Instantaneous Overcurrent 1 Pickup
5DA3
Ground Instantaneous Overcurrent 1 Delay
5DA4
Ground Instantaneous Overcurrent 1 Reset Delay
5DA5
Ground Instantaneous Overcurrent 1 Block
5DA7
Ground Instantaneous Overcurrent 1 Target
5DA8
Ground Instantaneous Overcurrent 1 Events
5DA9
Reserved (8 items)
5DB1
...Repeated for Ground Instantaneous Overcurrent 2
5DC2
...Repeated for Ground Instantaneous Overcurrent 3
5DD3
...Repeated for Ground Instantaneous Overcurrent 4
5DE4
...Repeated for Ground Instantaneous Overcurrent 5
5DF5
...Repeated for Ground Instantaneous Overcurrent 6
5E06
...Repeated for Ground Instantaneous Overcurrent 7
5E17
...Repeated for Ground Instantaneous Overcurrent 8
5E28
...Repeated for Ground Instantaneous Overcurrent 9
5E39
...Repeated for Ground Instantaneous Overcurrent 10
5E4A
...Repeated for Ground Instantaneous Overcurrent 11
5E5B
...Repeated for Ground Instantaneous Overcurrent 12
Incipient Cable Fault Detector Actual Values (Read Only) (6 modules)
5EC0
Incipient Cable Fault Detector 1 Phase A Counter
5EC1
Incipient Cable Fault Detector 1 Phase B Counter
5EC2
Incipient Cable Fault Detector 1 Phase C Counter
5EC3
...Repeated for Incipient Cable Fault Detector 2
5EC6
...Repeated for Incipient Cable Fault Detector 3
5EC9
...Repeated for Incipient Cable Fault Detector 4
5ECC
...Repeated for Incipient Cable Fault Detector 5
5ECF
...Repeated for Incipient Cable Fault Detector 6
Incipient Cable Fault Detector Command (Read Only) (6 modules)
5ED8
Incipient Cable Fault Detector 1 Clear Counters
5ED9
...Repeated for Incipient Cable Fault Detector 2
5EDA
...Repeated for Incipient Cable Fault Detector 3
5EDB
...Repeated for Incipient Cable Fault Detector 4
5EDC
...Repeated for Incipient Cable Fault Detector 5
5EDD
...Repeated for Incipient Cable Fault Detector 6
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
5F71
Setting Groups Block
5F73
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
5F7D
Setting Group Function
5F7E
Setting Group Events
Setting Groups (Read Only)
5F7F
Current Setting Group
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
5F94
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
GE Multilin
RANGE
0 to 1
0 to 5
0 to 30
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 5
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 5
---
---
---
---
---
---
F35 Multiple Feeder Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F126
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F001
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
DEFAULT
0 (Disabled)
0 (SRC 1)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
B
0
0
0
0 (No)
0
0
0
0 (Disabled)
0 (Disabled)
0
(none)
(none)
(none)
(none)
(none)
(none)
B-37

Advertisement

Table of Contents
loading

Table of Contents