Dielectric Strength; Control Power - GE UR F35 Series Instruction Manual

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

3 HARDWARE
The dielectric strength of the UR-series module hardware is shown in the following table:
Table 3–1: DIELECTRIC STRENGTH OF UR-SERIES MODULE HARDWARE
MODULE
MODULE FUNCTION
TYPE
1
Power supply
1
Power supply
1
Power supply
2
Reserved
3
Reserved
4
Reserved
5
Analog inputs/outputs
6
Digital contact inputs/
outputs
G.703
7
RS422
8
CT/VT
9
CPU
Filter networks and transient protection clamps are used in the hardware to prevent damage caused
by high peak voltage transients, radio frequency interference (RFI), and electromagnetic interference
(EMI). These protective components can be damaged by application of the ANSI/IEEE C37.90 spec-
ified test voltage for a period longer than the specified one minute.
Control power supplied to the relay must be connected to the matching power supply range of the
relay. If voltage is applied to the wrong terminals, damage can occur.
The F35 relay, like almost all electronic relays, contains electrolytic capacitors. These capacitors are
well-known to deteriorate over time if voltage is not applied periodically. Deterioration can be avoided
by powering up the relay at least once a year.
The power supply module can be ordered for two possible voltage ranges, and the UR can be ordered with or without a
redundant power supply module option. Each range has a dedicated input connection for proper operation. The ranges are
as shown below (see the Technical specifications section of chapter 2 for additional details):
Low (LO) range: 24 to 48 V (DC only) nominal
High (HI) range: 125 to 250 V nominal
The power supply module provides power to the relay and supplies power for dry contact input connections.
The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay (see the
Typical wiring diagram earlier). The critical failure relay is a form-C device that is energized once control power is applied
and the relay has successfully booted up with no critical self-test failures. If on-going self-test diagnostic checks detect a
critical failure (see the Self-test errors section in chapter 7) or control power is lost, the relay is de-energize.
For high reliability systems, the F35 has a redundant option in which two F35 power supplies are placed in parallel on the
bus. If one of the power supplies become faulted, the second power supply assumes the full load of the relay without any
interruptions. Each power supply has a green LED on the front of the module to indicate it is functional. The critical fail relay
of the module also indicates a faulted power supply.
GE Multilin
TERMINALS
FROM
High (+); Low (+); (–)
48 V DC (+) and (–)
Relay terminals
N/A
N/A
N/A
All except 8b
All
All except 2b, 3a, 7b, 8a
All except 6a, 7b, 8a
All
All
F35 Multiple Feeder Protection System

3.2.2 DIELECTRIC STRENGTH

DIELECTRIC STRENGTH
(AC)
TO
Chassis
2000 V AC for 1 minute
Chassis
2000 V AC for 1 minute
Chassis
2000 V AC for 1 minute
N/A
N/A
N/A
N/A
N/A
N/A
Chassis
< 50 V DC
Chassis
2000 V AC for 1 minute
Chassis
2000 V AC for 1 minute
Chassis
< 50 V DC
Chassis
2000 V AC for 1 minute
Chassis
2000 V AC for 1 minute

3.2.3 CONTROL POWER

3.2 WIRING
3
3-9