Relay Passwords; Flexlogic Customization - GE UR F35 Series Instruction Manual

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

1.5 USING THE RELAY
The settings for the relay can be programmed manually (see Chapter 5) via the faceplate keypad or remotely via the
1
EnerVista UR Setup software (see the EnerVista UR Setup help file).
a) PASSWORD SECURITY
It is recommended that passwords be set for each security level and assigned to specific personnel. There are two user
security access levels, COMMAND and SETTING.
1. COMMAND
The COMMAND access level restricts the user from making any settings changes, but allows the user to perform the fol-
lowing operations:
Change state of virtual inputs
Clear event records
Clear oscillography records
Operate user-programmable pushbuttons
2. SETTING
The SETTING access level allows the user to make any changes to any of the setting values.
See the Changing Settings section in Chapter 4 for complete instructions on setting security-level passwords.
NOTE
b) CYBERSENTRY
When the CyberSentry option is purchased, advanced security services are available, using either device authentication or
server authentication using RADIUS. When this option is purchased, the basic password security is disabled automatically.
For more information, see the CyberSentry content in the Security section of the next chapter.
FlexLogic equation editing is required for setting user-defined logic for customizing the relay operations. See the FlexLogic
section in Chapter 5.
1-20
F35 Multiple Feeder Protection System
1 GETTING STARTED

1.5.5 RELAY PASSWORDS

1.5.6 FLEXLOGIC CUSTOMIZATION