5.6 GROUPED ELEMENTS
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS
NEGATIVE SEQUENCE
CURRENT
For additional information on the negative sequence time overcurrent curves, see the Inverse Time Overcurrent Curves
section earlier.
b) NEGATIVE SEQUENCE TIME OVERCURRENT
(ANSI 51Q, IEC PTOC)
PATH: SETTINGS
GROUPED ELEMENTS
NEG SEQ TOC1
5
The negative-sequence time overcurrent element may be used to determine and clear unbalance in the system. The input
for calculating negative-sequence current is the fundamental phasor value.
Two methods of resetting operation are available; "Timed" and "Instantaneous" (refer to the Inverse Time Overcurrent Char-
acteristics sub-section for details on curve setup, trip times and reset operation). When the element is blocked, the time
accumulator resets according to the reset characteristic. For example, if the element reset characteristic is set to "Instanta-
neous" and the element is blocked, the time accumulator is cleared immediately.
5-150
SETTING GROUP 1(6)
NEG SEQ TOC1
NEG SEQ TOC2
MESSAGE
NEG SEQ IOC1
MESSAGE
NEG SEQ IOC2
MESSAGE
SETTING GROUP 1(6)
NEG SEQ TOC1
FUNCTION: Disabled
NEG SEQ TOC1 SIGNAL
MESSAGE
SOURCE: SRC 1
NEG SEQ TOC1
MESSAGE
PICKUP: 1.000 pu
NEG SEQ TOC1
MESSAGE
CURVE: IEEE Mod Inv
NEG SEQ TOC1
MESSAGE
TD MULTIPLIER: 1.00
NEG SEQ TOC1
MESSAGE
RESET: Instantaneous
NEG SEQ TOC1 BLOCK:
MESSAGE
Off
NEG SEQ TOC1
MESSAGE
TARGET: Self-reset
NEG SEQ TOC1
MESSAGE
EVENTS: Disabled
F35 Multiple Feeder Protection System
5.6.7 NEGATIVE SEQUENCE CURRENT
NEGATIVE SEQUENCE CURRENT
See page 5–150.
See page 5–150.
See page 5–151.
See page 5–151.
NEGATIVE SEQUENCE CURRENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.000 to 30.000 pu in steps of 0.001
Range: see OVERCURRENT CURVE TYPES table
Range: 0.00 to 600.00 in steps of 0.01
Range: Instantaneous, Timed
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS
NEG SEQ TOC1