Teleprotection Channel Tests; Incipient Fault Detector - GE UR F35 Series Instruction Manual

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

6 ACTUAL VALUES
b) SLOW EXCHANGE
PATH: ACTUAL VALUES
STATUS
 SLOW EXCHANGE 1
MESSAGE
These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size
for the slow EGD exchanges are displayed.
PATH: ACTUAL VALUES
STATUS
 TELEPROT CH TESTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The status information for two channels is shown here.
CHANNEL 1 STATUS: This represents the receiver status of each channel. If the value is "OK", teleprotection is
enabled and data is being received from the remote terminal; If the value is "FAIL", teleprotection enabled and data is
not being received from the remote terminal. If "n/a", teleprotection is disabled.
CHANNEL 1 LOST PACKETS: Data is transmitted to the remote terminals in data packets at a rate of two packets per
cycle. The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the

COMMANDS
CLEAR RECORDS
VALIDITY OF CHANNEL CONFIGURATION: This value displays the current state of the communications channel
identification check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the
"FAIL" message will be displayed. The "N/A" value appears if the local relay ID is set to a default value of "0", the chan-
nel is failed, or if the teleprotection inputs/outputs are not enabled.
PATH: ACTUAL VALUES
STATUS
 INCIPIENT FAULT 1
MESSAGE
MESSAGE
The number of detected incipient faults for each incipient fault element are displayed here for each phase. These values
can be reset to zero with the
COMMANDS
GE Multilin

EGD PROTOCOL STATUS
SLOW EXCHANGE 1
SIGNATURE:
0
SLOW EXCHANGE 1
DATA LENGTH:
0

TELEPROT CH TESTS
CHANNEL 1
STATUS: n/a
CHANNEL 1 LOST
PACKETS:
1
CHANNEL 2
STATUS: n/a
CHANNEL 2 LOST
PACKETS:
1
VALIDITY OF CHANNEL
CONFIGURATION: FAIL
menu.

INCIPIENT FAULT
INCIPIENT FAULT 1(6)
INCIPIENT FAULT 1
PH A FAULTS: 0
INCIPIENT FAULT 1
PH B FAULTS: 0
INCIPIENT FAULT 1
PH C FAULTS: 0

CLEAR RECORDS
F35 Multiple Feeder Protection System

PRODUCER STATUS
SLOW EXCHANGE 1(2)

6.2.19 TELEPROTECTION CHANNEL TESTS

Range: n/a, FAIL, OK
Range: 1 to 65535 in steps of 1
Range: n/a, FAIL, OK
Range: 1 to 65535 in steps of 1
Range: n/a, FAIL, OK

6.2.20 INCIPIENT FAULT DETECTOR

Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1

CLEAR INCIPENT FAULT COUNTERS
6.2 STATUS
6
command.
6-11