Table B–10: MODBUS MEMORY MAP (Sheet 39 of 61)
ADDR
REGISTER NAME
98A9
...Repeated for IEC61850 GOOSE uinteger 4
98AC
...Repeated for IEC61850 GOOSE uinteger 5
98AF
...Repeated for IEC61850 GOOSE uinteger 6
98B2
...Repeated for IEC61850 GOOSE uinteger 7
98B5
...Repeated for IEC61850 GOOSE uinteger 8
98B8
...Repeated for IEC61850 GOOSE uinteger 9
98BB
...Repeated for IEC61850 GOOSE uinteger 10
98BE
...Repeated for IEC61850 GOOSE uinteger 11
98C1
...Repeated for IEC61850 GOOSE uinteger 12
98C4
...Repeated for IEC61850 GOOSE uinteger 13
98C7
...Repeated for IEC61850 GOOSE uinteger 14
98CA
...Repeated for IEC61850 GOOSE uinteger 15
98CD
...Repeated for IEC61850 GOOSE uinteger 16
FlexElement Actual Values (Read Only) (16 modules)
9000
FlexElement 1 Actual
9902
FlexElement 2 Actual
9904
FlexElement 3 Actual
9906
FlexElement 4 Actual
9908
FlexElement 5 Actual
990A
FlexElement 6 Actual
990C
FlexElement 7 Actual
990E
FlexElement 8 Actual
9910
FlexElement 9 Actual
9912
FlexElement 10 Actual
9914
FlexElement 11 Actual
9916
FlexElement 12 Actual
9918
FlexElement 13 Actual
991A
FlexElement 14 Actual
991C
FlexElement 15 Actual
991E
FlexElement 16 Actual
Breaker Restrike (Read/Write Setting) (3 modules)
9930
Breaker Restrike 1 Function
9931
Breaker Restrike 1 Block
9933
Breaker Restrike 1 Signal Source
9934
Breaker Restrike 1 Pickup
9935
Breaker Restrike 1 Reset Delay
9936
Breaker Restrike 1 HF Detect
9937
Breaker Restrike 1 Breaker Open
9939
Breaker Restrike 1 Open Command
993B
Breaker Restrike 1 Close Command
993D
Breaker Restrike 1 Target
993E
Breaker Restrike 1 Events
993F
Reserved (2 items)
9941
...Repeated for Breaker Restrike 2
9952
...Repeated for Breaker Restrike 3
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9980
Teleprotection Clear Lost Packets
Teleprotection Inputs/Outputs (Read/Write Settings)
9990
Teleprotection Function
9991
Teleprotection Number of Terminals
9992
Teleprotection Number of Channels
9993
Teleprotection Local Relay ID
9994
Teleprotection Terminal 1 ID
9995
Teleprotection Terminal 2 ID
GE Multilin
RANGE
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
0 to 1
0 to 4294967295
0 to 5
0.10 to 2.00
0 to 65.535
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
---
0 to 1
0 to 1
2 to 3
1 to 2
0 to 255
0 to 255
0 to 255
F35 Multiple Feeder Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
1
F102
---
1
F300
---
1
F167
pu
0.01
F001
s
0.001
F001
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
---
F002
---
1
F126
---
1
F102
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
DEFAULT
B
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 (Disabled)
0
0 (SRC 1)
50
100
1 (Enabled)
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (No)
0 (Disabled)
2
1
0
0
0