5.7 CONTROL ELEMENTS
SETTING
COUNTER 1 FUNCTION:
Disabled = 0
Enabled = 1
SETTING
COUNTER 1 UP:
Off = 0
SETTING
COUNTER 1 DOWN:
Off = 0
SETTING
COUNTER 1 BLOCK:
Off = 0
SETTING
CNT 1 SET TO PRESET:
Off = 0
SETTING
COUNTER 1 RESET:
Off = 0
SETTING
COUNT1 FREEZE/RESET:
Off = 0
5
SETTING
COUNT1 FREEZE/COUNT:
Off = 0

PATH: SETTINGS
CONTROL ELEMENTS
 8-BIT
 SWITCH 1
5-146
SETTINGS
COUNTER 1 NAME:
AND
COUNTER 1 UNITS:
COUNTER 1 PRESET:
RUN
CALCULATE
VALUE
SET TO PRESET VALUE
SET TO ZERO
AND
AND
OR
STORE DATE & TIME
OR
Figure 5–73: DIGITAL COUNTER SCHEME LOGIC


8-BIT SWITCHES

8BIT SWITCH 1
FUNCTION: Disabled
8BIT SW 1 ARG A0:
MESSAGE
Off
8BIT SW 1 ARG A1:
MESSAGE
Off
8BIT SW 1 ARG A7:
MESSAGE
Off
8BIT SW 1 ARG B0:
MESSAGE
Off
8BIT SW 1 ARG B1:
MESSAGE
Off
8BIT SW 1 ARG B7:
MESSAGE
Off
8BIT SW 1 CONTROL:
MESSAGE
Off
F35 Multiple Feeder Protection System
SETTING
COUNTER 1 COMPARE:
Count more than Comp.
Count equal to Comp.
Count less than Comp.
ACTUAL VALUE
COUNTER 1 ACCUM:
ACTUAL VALUES
COUNTER 1 FROZEN:
Date & Time
8-BIT SWITCH 1(6)
Range: Disabled, Enabled
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
5 SETTINGS
FLEXLOGIC
OPERANDS
COUNTER 1 HI
COUNTER 1 EQL
COUNTER 1 LO
827065A1.VSD
5.7.9 8-BIT SWITCHES