B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 21 of 50)
ADDR
REGISTER NAME
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5E00
Ground Instantaneous Overcurrent 1 Signal Source
5E01
Ground Instantaneous Overcurrent 1 Function
5E02
Ground Instantaneous Overcurrent 1 Pickup
5E03
Ground Instantaneous Overcurrent 1 Delay
B
5E04
Ground Instantaneous Overcurrent 1 Reset Delay
5E05
Ground Instantaneous Overcurrent 1 Block
5E06
Ground Instantaneous Overcurrent 1 Target
5E07
Ground Instantaneous Overcurrent 1 Events
5E08
Reserved (8 items)
5E10
...Repeated for Ground Instantaneous Overcurrent 2
5E20
...Repeated for Ground Instantaneous Overcurrent 3
5E30
...Repeated for Ground Instantaneous Overcurrent 4
5E40
...Repeated for Ground Instantaneous Overcurrent 5
5E50
...Repeated for Ground Instantaneous Overcurrent 6
5E60
...Repeated for Ground Instantaneous Overcurrent 7
5E70
...Repeated for Ground Instantaneous Overcurrent 8
5E80
...Repeated for Ground Instantaneous Overcurrent 9
5E90
...Repeated for Ground Instantaneous Overcurrent 10
5EA0
...Repeated for Ground Instantaneous Overcurrent 11
5EB0
...Repeated for Ground Instantaneous Overcurrent 12
Incipient cable fault detector actual values (read only)
5EC0
Incipient cable fault detector 1 phase A counter
5EC1
Incipient cable fault detector 1 phase B counter
5EC2
Incipient cable fault detector 1 phase C counter
5EC3
...Repeated for incipient cable fault detector 2
5EC6
...Repeated for incipient cable fault detector 3
5EC9
...Repeated for incipient cable fault detector 4
5ECC
...Repeated for incipient cable fault detector 5
5ECF
...Repeated for incipient cable fault detector 6
Setting Groups (Read/Write Setting)
5F80
Setting Group for Modbus Comms (0 means group 1)
5F81
Setting Groups Block
5F82
FlexLogic to Activate Groups 2 through 6 (5 items)
5F89
Setting Group Function
5F8A
Setting Group Events
Setting Groups (Read Only)
5F8B
Current Setting Group
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
5F94
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
Autoreclose (Read/Write Setting) (6 modules)
6240
Autoreclose 1 Function
6241
Autoreclose 1 Initiate
6242
Autoreclose 1 Block
6243
Autoreclose 1 Max Number of Shots
6244
Autoreclose 1 Manual Close
6245
Autoreclose 1 Manual Reset from LO
6246
Autoreclose 1 Reset Lockout if Breaker Closed
6247
Autoreclose 1 Reset Lockout On Manual Close
B-28
RANGE
0 to 5
0 to 1
0 to 30
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 5
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 5
---
---
---
---
---
---
0 to 1
0 to 65535
0 to 65535
1 to 4
0 to 65535
0 to 65535
0 to 1
0 to 1
F35 Multiple Feeder Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F167
---
1
F102
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F001
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
1
F102
---
1
F300
---
1
F300
---
1
F001
---
1
F300
---
1
F300
---
1
F108
---
1
F108
DEFAULT
0 (SRC 1)
0 (Disabled)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0
0
0
0
0
0
0 (Disabled)
0 (Disabled)
0
(none)
(none)
(none)
(none)
(none)
(none)
0 (Disabled)
0
0
1
0
0
0 (Off)
0 (Off)
GE Multilin