GE UR F35 Series Instruction Manual page 223

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

5 SETTINGS
Table 5–8: F35 FLEXLOGIC™ OPERANDS (Sheet 5 of 6)
OPERAND TYPE
OPERAND SYNTAX
INPUTS/OUTPUTS:
Cont Op 1
Contact outputs,
Cont Op 2
voltage
(from detector on
Cont Op 1
form-A output only)
Cont Op 2
INPUTS/OUTPUTS
DIRECT INPUT 1 On
Direct inputs
DIRECT INPUT 32 On
INPUTS/OUTPUTS:
RemDPS Ip 1 BAD
Remote double-
RemDPS Ip 1 INTERM
point status inputs
RemDPS Ip 1 OFF
RemDPS Ip 1 ON
REMDPS Ip 2...
INPUTS/OUTPUTS:
REMOTE INPUT 1 On
Remote inputs
REMOTE INPUT 32 On
INPUTS/OUTPUTS:
Virt Ip 1
Virtual inputs
Virt Ip 64
INPUTS/OUTPUTS:
Virt Op 1
Virtual outputs
Virt Op 96
LED INDICATORS:
LED IN SERVICE
Fixed front panel
LED TROUBLE
LEDs
LED TEST MODE
LED TRIP
LED ALARM
LED PICKUP
LED VOLTAGE
LED CURRENT
LED FREQUENCY
LED OTHER
LED PHASE A
LED PHASE B
LED PHASE C
LED NEUTRAL/GROUND
LED INDICATORS:
LED TEST IN PROGRESS
LED test
LED INDICATORS:
LED USER 1
User-programmable
LED USER 2 to 48
LEDs
PASSWORD
ACCESS LOC SETG OFF
SECURITY
ACCESS LOC SETG ON
ACCESS LOC CMND OFF
ACCESS LOC CMND ON
ACCESS REM SETG OFF
ACCESS REM SETG ON
ACCESS REM CMND OFF
ACCESS REM CMND ON
UNAUTHORIZED ACCESS
REMOTE DEVICES
REMOTE DEVICE 1 On
REMOTE DEVICE 16 On
REMOTE DEVICE 1 Off
REMOTE DEVICE 16 Off
RESETTING
RESET OP
RESET OP (COMMS)
RESET OP (OPERAND)
RESET OP (PUSHBUTTON)
GE Multilin
OPERAND DESCRIPTION
VOn
(will not appear unless ordered)
VOn
(will not appear unless ordered)
VOff
(will not appear unless ordered)
VOff
(will not appear unless ordered)
Flag is set, logic=1
Flag is set, logic=1
Asserted while the remote double-point status input is in the bad state.
Asserted while the remote double-point status input is in the intermediate
state.
Asserted while the remote double-point status input is off.
Asserted while the remote double-point status input is on.
Same set of operands as per REMDPS 1 above
Flag is set, logic=1
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
Asserted when the front panel IN SERVICE LED is on.
Asserted when the front panel TROUBLE LED is on.
Asserted when the front panel TEST MODE LED is on.
Asserted when the front panel TRIP LED is on.
Asserted when the front panel ALARM LED is on.
Asserted when the front panel PICKUP LED is on.
Asserted when the front panel VOLTAGE LED is on.
Asserted when the front panel CURRENT LED is on.
Asserted when the front panel FREQUENCY LED is on.
Asserted when the front panel OTHER LED is on.
Asserted when the front panel PHASE A LED is on.
Asserted when the front panel PHASE B LED is on.
Asserted when the front panel PHASE C LED is on.
Asserted when the front panel NEUTRAL/GROUND LED is on.
An LED test has been initiated and has not finished.
Asserted when user-programmable LED 1 is on.
The operand above is available for user-programmable LEDs 2 through 48.
Asserted when local setting access is disabled.
Asserted when local setting access is enabled.
Asserted when local command access is disabled.
Asserted when local command access is enabled.
Asserted when remote setting access is disabled.
Asserted when remote setting access is enabled.
Asserted when remote command access is disabled.
Asserted when remote command access is enabled.
Asserted when a password entry fails while accessing a password protected
level of the F35.
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Reset command is operated (set by all three operands below).
Communications source of the reset command.
Operand (assigned in the
of the reset command.
Reset key (pushbutton) source of the reset command.
F35 Multiple Feeder Protection System
5.5 FLEXLOGIC™