APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 50 of 50)
ADDR
REGISTER NAME
D3E4
...Repeated for Remote Device 26
D3E8
...Repeated for Remote Device 27
D3EC
...Repeated for Remote Device 28
D3F0
...Repeated for Remote Device 29
D3F4
...Repeated for Remote Device 30
D3F8
...Repeated for Remote Device 31
D3FC
...Repeated for Remote Device 32
Setting file template values (read only)
ED00
FlexLogic™ displays active
ED01
Reserved (6 items)
ED07
Last settings change date
ED09
Template bitmask (750 items)
F001
UR_UINT16 UNSIGNED 16 BIT INTEGER
F002
UR_SINT16 SIGNED 16 BIT INTEGER
F003
UR_UINT32 UNSIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register.
Low order word is stored in the second register.
F004
UR_SINT32 SIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register/
Low order word is stored in the second register.
F005
UR_UINT8 UNSIGNED 8 BIT INTEGER
F006
UR_SINT8 SIGNED 8 BIT INTEGER
F011
UR_UINT16 FLEXCURVE DATA (120 points)
A FlexCurve is an array of 120 consecutive data points (x, y) which
are interpolated to generate a smooth curve. The y-axis is the user
defined trip or operation time setting; the x-axis is the pickup ratio
and is pre-defined. Refer to format F119 for a listing of the pickup
ratios; the enumeration value for the pickup ratio indicates the off-
set into the FlexCurve base address where the corresponding time
value is stored.
GE Multilin
RANGE
0 to 1
---
0 to 4294967295
0 to 65535
F012
DISPLAY_SCALE DISPLAY SCALING
(unsigned 16-bit integer)
MSB indicates the SI units as a power of ten. LSB indicates the
number of decimal points to display.
Example: Current values are stored as 32 bit numbers with three
decimal places and base units in Amps. If the retrieved value is
12345.678 A and the display scale equals 0x0302 then the dis-
played value on the unit is 12.35 kA.
F013
POWER_FACTOR (SIGNED 16 BIT INTEGER)
Positive values indicate lagging power factor; negative values
indicate leading.
F040
UR_UINT48 48-BIT UNSIGNED INTEGER
F050
UR_UINT32 TIME and DATE (UNSIGNED 32 BIT INTEGER)
Gives the current time in seconds elapsed since 00:00:00 January
1, 1970.
F051
UR_UINT32 DATE in SR format (alternate format for F050)
First 16 bits are Month/Day (MM/DD/xxxx). Month: 1=January,
2=February,...,12=December; Day: 1 to 31 in steps of 1
Last 16 bits are Year (xx/xx/YYYY): 1970 to 2106 in steps of 1
F052
UR_UINT32 TIME in SR format (alternate format for F050)
First 16 bits are Hours/Minutes (HH:MM:xx.xxx).
Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm;
Minutes: 0 to 59 in steps of 1
F35 Multiple Feeder Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
---
---
---
1
F050
---
1
F001

B.4.2 DATA FORMATS

DEFAULT
B
1 (Enabled)
---
0
0
B-57