APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 36 of 50)
ADDR
REGISTER NAME
B0E8
IEC 61850 MMXU VAr.phsC Deadband 1
B0EA
IEC 61850 MMXU VA.phsA Deadband 1
B0EC
IEC 61850 MMXU VA.phsB Deadband 1
B0EE
IEC 61850 MMXU VA.phsC Deadband 1
B0F0
IEC 61850 MMXU PF.phsA Deadband 1
B0F2
IEC 61850 MMXU PF.phsB Deadband 1
B0F4
IEC 61850 MMXU PF.phsC Deadband 1
B0F6
...Repeated for Deadband 2
B12C
...Repeated for Deadband 3
B162
...Repeated for Deadband 4
B198
...Repeated for Deadband 5
B1CE
...Repeated for Deadband 6
IEC 61850 Report Settings (Read/Write Setting) (14 modules)
B280
IEC 61850 Report Control 1 RptID
B2A1
IEC 61850 Report Control 1 OptFlds
B2A2
IEC 61850 Report Control 1 BufTm
B2A4
IEC 61850 Report Control 1 TrgOps
B2A5
IEC 61850 Report Control 1 IntgPd
B2A7
...Repeated for Report 2
B2CE
...Repeated for Report 3
B2F5
...Repeated for Report 4
B31C
...Repeated for Report 5
B343
...Repeated for Report 6
B36A
...Repeated for Report 7
B391
...Repeated for Report 8
B3B8
...Repeated for Report 9
B3DF
...Repeated for Report 10
B406
...Repeated for Report 11
B42D
...Repeated for Report 12
B454
...Repeated for Report 13
B47B
...Repeated for Report 14
B4A2
...Repeated for Report 15
B4C9
...Repeated for Report 16
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
B500
Number of Status Indications in GGIO1
B501
IEC 61850 GGIO1 Indication operands (128 items)
IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules)
B5A0
IEC 61850 Configurable GOOSE Function
B5A1
IEC 61850 Configurable GOOSE ID
B5C2
Configurable GOOSE Destination MAC Address
B5C5
IEC 61850 Configurable GOOSE VLAN Transmit Priority
B5C6
IEC 61850 Configurable GOOSE VLAN ID
B5C7
IEC 61850 Configurable GOOSE ETYPE APPID
B5C8
IEC 61850 Configurable GOOSE ConfRev
B5CA
IEC 61850 Configurable GOOSE Retransmission Curve
B5CB
Configurable GOOSE Dataset Items for Transmission
(64 items)
B60B
...Repeated for Module 2
B676
...Repeated for Module 3
B6E1
...Repeated for Module 4
B74C
...Repeated for Module 5
B7B7
...Repeated for Module 6
B822
...Repeated for Module 7
B88D
...Repeated for Module 8
GE Multilin
RANGE
0.001 to 100
0.001 to 100
0.001 to 100
0.001 to 100
0.001 to 100
0.001 to 100
0.001 to 100
---
0 to 65535
0 to 4294967295
0 to 65535
0 to 4294967295
8 to 128
---
0 to 1
---
---
0 to 7
0 to 4095
0 to 16383
1 to 4294967295
0 to 3
0 to 542
F35 Multiple Feeder Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
%
0.001
F003
%
0.001
F003
%
0.001
F003
%
0.001
F003
%
0.001
F003
%
0.001
F003
%
0.001
F003
---
---
F209
---
1
F001
---
1
F003
---
1
F001
---
1
F003
---
8
F001
---
1
F300
---
1
F102
---
---
F209
"GOOSEOut_x_"
---
---
F072
---
1
F001
---
1
F001
---
1
F001
---
1
F003
---
1
F611
---
1
F232
DEFAULT
10000
10000
10000
10000
10000
B
10000
10000
0
0
0
0
8
0
0 (None)
0
4
0
0
1
3 (Relaxed)
0 (None)
B-43