5 SETTINGS
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 COMMUNICATIONS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
b) SERIAL PORTS
PATH: SETTINGS
PRODUCT SETUP
 SERIAL PORTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The F35 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for
local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet
or RS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate and parity. It is important that
GE Multilin


COMMUNICATIONS

 SERIAL PORTS
 NETWORK
 MODBUS PROTOCOL
 DNP PROTOCOL
 DNP / IEC104
 POINT LISTS
 IEC 61850 PROTOCOL
 WEB SERVER
 HTTP PROTOCOL
 TFTP PROTOCOL
 IEC 60870-5-104
 PROTOCOL
 SNTP PROTOCOL
 EGD PROTOCOL
 ETHERNET SWITCH

COMMUNICATIONS
SERIAL PORTS
RS485 COM1 BAUD
RATE: 19200
RS485 COM1 PARITY:
None
RS485 COM1 RESPONSE
MIN TIME:
0 ms
RS485 COM2 BAUD
RATE: 19200
RS485 COM2 PARITY:
None
RS485 COM2 RESPONSE
MIN TIME:
0 ms
F35 Multiple Feeder Protection System
5.2 PRODUCT SETUP
5.2.4 COMMUNICATIONS
See below.
See page 5–16.
See page 5–16.
See page 5–17.
See page 5–20.
See page 5–21.
See page 5–32.
See page 5–32.
See page 5–32.
See page 5–33.
See page 5–33.
See page 5–35.
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200. Only
active if CPU Type E is ordered.
Range: None, Odd, Even
Only active if CPU Type E is ordered
Range: 0 to 1000 ms in steps of 10
Only active if CPU Type E is ordered
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200
Range: None, Odd, Even
Range: 0 to 1000 ms in steps of 10
5