10.5 Operating modes of the CPU
Reference
Additional information about cycle and response times is available in the Function Manual
Cycle and response times (http://support.automation.siemens.com/WW/view/en/59193558).
10.5.4

Operating mode transitions

Operating modes and operating mode transitions
The following figure shows the operating modes and the operating mode transitions:
Figure 10-3
The table below shows the effects of the operating mode transitions:
Table 10- 4
Operating mode transitions
N o .
Op e rating mode transitions
POWER ON →
STARTUP
POWER ON →
STOP
174
Operating modes and operating mode transitions
After switching on, the CPU switches to
"STARTUP" mode if:
The hardware configuration and program
blocks are consistent.
Startup type "Warm restart - RUN" is set
or
Startup type "Warm restart mode before
POWER OFF" is set and the CPU was
in RUN mode before POWER OFF.
After switching on, the CPU goes to "STOP"
mode if:
The hardware configuration and program
blocks are inconsistent
or
Startup type "No restart" is set.
or
Startup type "Warm restart mode before
POWER OFF" is set and the CPU was
in STOP mode before POWER OFF.
Effects
Non-retentive memory is cleared, and the content
of non-retentive DBs is reset to the start values of
the load memory. Retentive memory and reten-
tive DB contents are retained.
Non-retentive memory is cleared, and the content
of non-retentive DBs is reset to the start values of
the load memory. Retentive memory and reten-
tive DB contents are retained.
System Manual, 09/2016, A5E03461182-AD