3.1.3
Hardware configuration of the ET 200MP distributed I/O system with
PROFIBUS interface module
M aximum configuration
The integrated system power supply of the interface module feeds 14 W into the backplane
bus. The power budget calculation determines the exact number of I/O modules that can be
operated with the interface module. The operating principle is described in section Power
balance calculation (Page 45).
Figure 3-3
Applicable modules
The following table shows which modules may be used in the various slots:
Table 3- 3
Mo dule type
Interface module
Analog and digital I/O modules
Communications modules
Technology modules
Automation system
System Manual, 09/2016, A5E03461182-AD
Maximum configuration ET 200MP with IM 155-5 DP
Assignment of slot numbers
Point-to-point
Pe rmissible slots
Ma ximum number of modules
2
1
3 - 14
12
3 - 14
12
3 - 14
12
Application planning
3.1 Hardware configuration