Procedure
To set up the configuration control, follow these steps in the order given:
Table 9- 1
Procedure for commissioning the SIMATIC S7-1500
Ste p
Pro cedure
1
Enable configuration control in STEP 7
2
Create control data record
3
Transfer control data record
Block library "OH_S71x00_Library"
The block library OH_S71x00_Library
(https://support.industry.siemens.com/cs/ww/en/view/29430270) is available for download
from the Internet. The block library contains data types with the structure of the control data
records for the S7-1500/ET 200MP. You can implement your flexible automation solution
economically with the help of these data types.
9.2.1

Configuring

Requirements
With the S7-1500, configuration control is possible both with centrally inserted modules and
with the ET 200MP distributed I/O system via PROFINET IO.
For S 7-1500 automation system:
● STEP 7 Professional as of Version V13
● CPU S7-15XX as of firmware version V1.5
● The startup parameter "Comparison preset to actual configuration" is set to "Startup CPU
even if mismatch" (default setting).
You can find the "Comparison preset to actual configuration" parameter in the Inspector
window of the CPU properties under "General">"Startup".
For E T 200MP distributed I/O system:
● STEP 7 Professional as of Version V13
● IM 155-5 PN ST/HF
● You have assigned the interface module to an IO controller/DP master in STEP 7
● The startup parameter "Comparison preset to actual module" is set to "Startup CPU even
if mismatch" (default setting).
You can find the "Comparison preset to actual module" parameter in the Inspector
window of the interface module properties in the "Startup" field under "General">"Module
parameters".
Automation system
System Manual, 09/2016, A5E03461182-AD
9.2 Configuration control (option handling)
Se e...
Section Configuring (Page 145)
Section Creating the control data record (Page 147)
Section Transferring the control data record in the
startup program of the CPU (Page 156)
Flexible automation concepts
145

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et200mp

Table of Contents