6. Remove the SIMATIC memory card after the firmware update is complete.
The RUN LED on the CPU lights up yellow, the MAINT LED flashes yellow.
If you use the SIMATIC memory card subsequently as a program card, delete the
firmware update files manually. Optionally, you can perform this action directly on the
CPU display. To do so, after completion of the firmware update, select the "Convert
memory card" menu item on the display.
Not e
If your hardware configuration contains several modules, the CPU updates all affected
module in the slot sequence, i.e. in ascending order of the module position in the STEP 7
device configuration.
Not e
Memory s ize of the SIMATIC memory card
If you perform a firmware update via the SIMATIC memory card, you must use a large
enough card based on the CPU used and the associated I/O modules.
Therefore, be sure to note the file size of the update files when downloading them from the
Product Support website. The file size information is especially important when you perform
the firmware update not only for the CPU but also for the associated I/O modules,
communication modules, etc. The total size of the update files must not exceed the available
memory size of your SIMATIC memory card.
Procedure: via the integrated Web server
The procedure is described in the Web server
(http://support.automation.siemens.com/WW/view/en/59193560) Function Manual.
Procedure: online v ia the SIMATIC Automation Tool
The procedure is described in the SIMATIC Automation Tool
(https://support.industry.siemens.com/cs/ww/de/view/98161300) manual (included in the
SIMATIC Automation Tool).
Special feature at a firmware update of analog modules
If you want to carry out a firmware update for analog modules, you have to supply 24 V DC
load supply to the module through the power supply element.
Behavior after the firmware update
After the firmware update, check the firmware version of the updated module.
Automation system
System Manual, 09/2016, A5E03461182-AD
Maintenance
13.4 Firmware update
217