Commissioning
10.4 Procedure for commissioning the ET 200MP distributed I/O system
10.4
Procedure for commissioning the ET 200MP distributed I/O system
10.4.1
Commissioning the ET 200MP for PROFINET IO
Introduction
The commissioning of your automation system depends on the plant configuration.
The following procedure describes the commissioning of the distributed I/O system on an IO
controller.
Commissioning procedure
To commission the ET 200MP as an IO device for PROFINET IO, we recommend the
following procedure:
Table 10- 2
Ste p
1
2
4
5
6
7
8
9
10
Not e
The operating mode transitions for the IO controller from RUN to STOP or from STOP to
RUN can take several milliseconds, until the mode transition for the inputs and outputs of all
I/O modules for the ET 200MP station is completed. This delay also applies to isochronous
mode.
168
Procedure for commissioning the ET 200MP as an IO device for PROFINET IO
Pro cedure
Install ET 200MP
Connect ET 200MP
Supply voltages
•
PROFINET IO
•
Sensors and actuators
•
Configure IO controller
Switch on supply voltages for the IO
controller
Switch on supply voltages for IO
devices
Download configuration to the IO
controller
Switch IO controller to RUN mode
Check LEDs
Test inputs and outputs
Se e...
Section Installation (Page 48)
Section Wiring (Page 63)
CPU manual or documentation of the IO controller
CPU manual or documentation of the IO controller
Interface module
(http://support.automation.siemens.com/WW/view/en
/67295970/133300) manual
STEP 7 online help
CPU manual or documentation of the IO controller
Interface module
(http://support.automation.siemens.com/WW/view/en
/67295970/133300) manual
The following functions are helpful: Monitoring and
modifying tags, testing with program status, forcing,
modifying the outputs. See section Test functions
and fault resolution (Page 225)
System Manual, 09/2016, A5E03461182-AD
Automation system