10.4.2
Commissioning the ET 200MP for PROFIBUS DP
Introduction
The commissioning of your automation system depends on the plant configuration.
The following procedure describes the commissioning of the ET 200MP distributed
I/O system on a DP master.
Commissioning procedure
To commission the ET 200MP as a DP slave for PROFIBUS DP, we recommend the
following procedure:
Table 10- 3
Ste p
1
2
3
4
5
6
7
8
9
10
Not e
During operating mode transitions of the DP master from RUN to STOP or from STOP to
RUN, it can take several milliseconds until the mode transition for the inputs and outputs of
all I/O modules of the ET 200MP is complete.
Automation system
System Manual, 09/2016, A5E03461182-AD
10.4 Procedure for commissioning the ET 200MP distributed I/O system
Procedure for commissioning the ET 200MP as a DP slave for PROFIBUS DP
Pro cedure
Install ET 200MP (with IM 155-5 DP ST)
Set the PROFIBUS address on the inter-
face module
Connect ET 200MP
Supply voltages
•
PROFIBUS DP
•
Sensors and actuators
•
Configure DP master (including
PROFIBUS address)
Switch on supply voltages for DP master Documentation of the DP master
Switch on supply voltages for DP slaves
Download configuration to the DP mas-
ter
Switch DP master to RUN
Check LEDs
Test inputs and outputs
Se e...
Section Installation (Page 48)
Manual for the interface module
(http://support.automation.siemens.com/WW/view
/en/77910801/133300)
Section Wiring (Page 63)
Documentation of the DP master
Interface module
(http://support.automation.siemens.com/WW/view
/en/77910801/133300) manual
STEP 7 online help
Documentation of the DP master
Interface module
(http://support.automation.siemens.com/WW/view
/en/77910801/133300) manual
The following functions are helpful: Monitoring
and modifying tags, testing with program status,
forcing, modifying the outputs. See section Test
functions and fault resolution (Page 225)
Commissioning
169