Index 4011H) Inverter Status (R) - Mitsubishi Electric FR-A7NCA Instruction Manual

Table of Contents

Advertisement

OBJECT DICTIONARY

8.3.14 (Index 4011h) Inverter Status (r)

Sub Index
Data type
Default value
00h
Access attribute
Availability of mapping to PDO Enable
<Detail>
Read the inverter status.
Bit definitions are as follows.
bit
0
RUN (inverter running)
1
FWD (During forward rotation)
2
REV (Reverse running)
3
SU (up-to-frequency)
4
OL (overload)
5
IPF (instantaneous power failure)
6
FU (frequency detection)
7
ABC1 (alarm)
8 to 14 (blank)
15
Operation ready completion (READY)
108
Item
Name
Inverter Status (r)
UNSIGNED16 (16 bit unsigned)
Unit
Read Only
Definition
Signals are not affected by
settings of Pr.190 to Pr.196
(output terminal function
selection).
Description