Communication with the PLC
Check whether the output OUT0 „Enable" has switched to HIGH (ready for operation), otherwise there is a fault
condition.
Before starting measurement, all inputs must be switched to LOW for 30 ms.
Switch the input IN1 „Measurement Start" to HIGH.
Within 30 ms, the outputs OUT 1-3 have switched to HIGH for the duration of the measurement
(system reaction time, see chapter 2.2 - depending on material and thickness).
The measurement result is available after the systems reaction time t
starts again. An additional recovering time of 0.5 seconds is awaited (for FE material).
The measurement result of the 2nd measurement is available at the outputs. The measurement starts again.
Switch the input IN1 „Measurement Start" to LOW.
The measurement is aborted, the last measurement result is now available at the outputs OUT1-3. The measurement result
is frozen until a new cycle is initiated.
Example with „fast" PLC / BUS cycle time (< 20 ms):
Check whether the output OUT0 „Enable" has switched to HIGH.
All inputs must be LOW for more then 30 ms.
Then switch input IN1 „Measurement Start" to HIGH.
Check whether all outputs OUT1-3 switch to HIGH within 30 ms.
Continue to interrogate the outputs OUT1-3, until (after the systems reaction time t
available.
If required, interrogate several measurements.
Then switch input IN1 to LOW.
The measurement is aborted, the last measurement result is now available at the outputs OUT1-3. The measurement result
is frozen until a new cycle is initiated.
Example with „slow" PLC / BUS cycle time (> 20 ms):
Check whether the output OUT0 „Enable" has switched to HIGH.
All inputs must be LOW for more then 30 ms.
Then switch input IN1 „Measurement Start" to HIGH.
Continue to interrogate the outputs OUT1-3 until (after the systems reaction time t
available.
If required interrogate several measurements.
Then switch input IN1 to LOW.
The measurement is aborted, the last measurement result is now available at the outputs OUT1-3. The measurement result
is frozen until a new cycle is initiated.
76
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Detector R1000 series UDK20
Manual
at the outputs OUT1-3. The measurement
s
) the measurement result is
s
) the measurement result is
s
B0048991 / Rev. 1.3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents